DIN Series
240~960W Slim 3-phase High Input Voltage
TDR - 240
TDR - 480
TDR - 960
-
3-phase, 340~550VAC wide range input
(2-phase operation possible)
-
Slim width
-
Built-in active PFC function (TDR-480/960)
-
Built-in passive PFC function (TDR-240)
-
High efficiency up to 94.5%
-
Protections:
Short circuit / Overload / Over voltage / Over temperature
-
Cooling by free air convection
-
DC output voltage adjustable
-
Built-in constant current limiting circuit
-
Can be installed on DIN rail TS-35/7.5 or 15
-
UL508 / UL61010-1 Industrial control equipment approved
-
Current sharing up to 3840W(3+1) for TDR-960
-
Built-in DC OK relay contact (optional for TDR-480)
-
3 years warranty
Features
Model No
TDR-240
AC input voltage range
3-phase 340~550VAC (2-phase operation possible), 480~780VD
AC inrush current (max.)
0.69A / 400VAC, 0.6A / 500VAC
General Specification (Please refer to www.meanwell.com for detail spec.)
DC adjustment range
29~33V for 24V model, 56~65V for 48V model (30~36V for TDR-240-24)
Overload protection
Shut down o/p voltage, auto-recovery after temperature goes down
I/P-O/P:4.87kVAC I/P-FG:2.4kVAC
O/P-FG:0.5kVAC O/P-DC OK: 0.5kVAC
12V: 12~14V, 24V: 24~28V, 48V: 48~55
105%~130% rated output power, constant current limiting, unit will shut down after 3 sec., re-power on to recover 105%~130% rated output power, constant current limiting, unit will hiccup after 3 sec.(TDR-240)
Overload protection
Shut down o/p voltage, re-power on to recover
Hiccup mode, recovers automatically after temperature goes down
240W
Model No
Output
Tol.
Effi.
R&N
TDR-240-24
24V, 0~10A
±1.0%
48V, 0~5A
TDR-240-48
±1.0%
100mV
120mV
92%
92%
Series
Difference
Range
EMC standards
-30~+70°C (refer to output derating curve)
UL61010-1, UL61010-2-201,
AS/NZS62368.1, EAC TP TC 004,
BS EN/EN61558-2-16 approved
BS EN/EN55032 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN55024,EN61000-6-2, heavy industry level; EAC TP TC 020
TDR-480
NDR-960
0.69A / 400VAC, 0.6A / 500VAC
2.0A / 400VAC, 1.4A / 500VA
Type
Over temperature protection
Withstand voltage
I/P-O/P:3kVAC I/P-FG:2kVAC O/P-FG:0.5kVAC
O/P-DC OK: 0.5kVAC(TDR-960; optional for TDR-480)
Working temperature
Safety standards
L508, IEC62368-1, AS/NZS62368.1, EAC TP TC 004 approved; UL62368-1 for TDR-480
I/P: 4 poles, O/P: 4 poles
I/P: 4 poles, O/P: 6 poles
Connection
(screw DIN terminal)
63x 125.2x 113.5
Dimension (WxHxD)(mm)
240W
Model No
Output
Tol.
Effi.
R&N
TDR-480-24
24V, 0~20A
±1.0%
48V, 0~10A
TDR-480-48
±1.0%
150mV
150mV
92.5%
93%
960W
Model No
Output
Tol.
Effi.
R&N
TDR-960-24
24V, 0~40A
±1.0%
48V, 0~20A
TDR-960-48
±1.0%
180mV
120mV
94.0%
94.5%
AC Input Voltage
WDR
TDR
1φ; 180~550VAC
3φ; 340~550VAC
85.5x 125.2x 128.5
110x125.2x150