Security Series
240~480W All-In-One Security Power
DRS-240
DRS-480
-
All-in-one function with Power supply, DC-UPS, battery charger
and status monitoring in ONE compact unit
-
Universal input 90~305VAC (277VAC available)
-
From C relay contacts and LED indicator for AC fail,bat low,
Charger Circuit fail,DC OK
-
Built-in MODBus protocol, CANBus optional
-
Charging curve can be set with SBP-001(see page97)
-
20~100% charging current adjustable by VR
-
2 or 3-stage selectable by DIP S.W, suitable for
lead acid and li-ion batteries
-
Load-dependent high speed battery charging
-
Proections:OLP/OTP/OVP/BAT cut off/
BAT reverse polarity(NO damage)
-
-30~+70℃ wide operating temp
-
Signal and alarms design meet UL2524,NFPA 1221 ,BS EN/EN54-4
and GB17945 requirement
-
3 years warranty
Features
10W
10W
Model No
Output
Tol.
Effi.
R&N
DRS-240-12
5V, 0~14A
±1%
DRS-240-36
24V, 0~10A
36V, 0~6.6A
DRS-240-24
Model No
DRS-240
DRS-480
AC input voltage range
90~305VAC; 127~431VDC
Total O/P Power
Combined power on all channels 240W (DRS-240)/480W(DRS-480)
General Specification (Please refer to www.meanwell.com for detail spec.)
Withstand voltage
UL62368-1,DEKRA BS EN/EN62368-1, EAC TP TC004 approved
BS EN/EN55032 class B, EN61000-4-2,3,4,5,6,8; BS EN/EN54-4 for fire and fire alarm system
Functions
Relay contact, Relay ON:DC OK, Relay OFF:charger fail
Signals normal DC output and activates when output voltage>90% rated
Relay contact, Relay ON:Bat. OK, Relay OFF:Bat.low
BAT.low voltage:<11V, <22V, <33V, <44V
Restart system directly form bat.and does not reguire AC power
I/P-O/P:4kVAC I/P-FG:2kVAC O/P-FG:1.5kVAC
-30~+70°C (refer to output derating curve)
Working temperature
Safety standards
EMC standards
Signals AC failure and activates when input voltage drops below:85~90% of 120Vac,60~85% of 220Vac
48V, 0~5A
DRS-240-48
±1%
±1%
±1%
120mV
240mV
360mV
480mV
92%
93%
94%
94%
480W
DRS-480
Model No
Output
Tol.
Effi.
R&N
DRS-480-24
24V, 0~20A
±2%
DRS-480-48
36V, 0~13.3A
48V, 0~10A
DRS-480-36
±1%
±1%
240mV
360mV
480mV
93%
94%
94%
I/P: 3 poles, O/P: 3 poles screw DIN terminal
From-C
Relay
AC fail
charger circuit fail
DC OK
Bot.low/ Abnormal/ Disconnected
BAT.start
Charging current Adj.
DC UPS
Communication
Dimension (WxHxD)(mm)
20~100% charging current adjustable by VR
UPS switch to bat. within 10ms of AC failure
Built-in MODBUS protocal,CANBus optional
85.5x 125.2x 128.5
12V, 0~20A
110x 125.2x 150