DIN Series
10~96W Ultra Slim
MDR-10
MDR-20
MDR-40
MDR-60
MDR-100
-
Universal AC input / Full range
-
Installed on DIN rail TS-35 / 7.5 or 15
-
Protections: Short circuit / Overload / Over voltage
-
No load power consumption <0.75W (<1W for MDR-100)
-
LED indicator for power on
-
Built-in active PFC and over temp. protection (MDR-100)
-
Class I, Div 2 Hazardous Locations T4(MDR-40/60)
-
DC OK signal output (MDR-10/20);
DC OK relay contact (MDR-40/60/100) -
Cooling by free air convection
-
DC output voltage adjustable (MDR-20~100)
-
3 years warranty
Feature
87%
60 W
Model No
Output
Tol.
R&N
Effi.
MDR-60-5
5V, 0~10.0A
±2%
80mV
78%
MDR-60-12
12V, 0~8.5A
±1%
120mV
86%
MDR-60-24
24V, 0~2.50A
±1%
150mV
88%
MDR-60-48
48V, 0~1.25A
±1%
200mV
10W
Model No
Output
Tol.
R&N
Effi.
MDR-10-5
5V, 0~2.0A
±5%
80mV
77%
MDR-10-15
12V, 0~0.84A
15V, 0~0.67A
120mV
81%
MDR-10-12
24V, 0~0.42A
±3%
120mV
81%
MDR-10-24
±2%
±3%
150mV
84%
Model No
MDR-10
MDR-20
MDR-40
MDR-60
AC input voltage range
85~264VAC; 120~370VDC
AC inrush current
Cold start, 35A at 115VAC, 70A at 230VAC
Cold start, 20A at 115VAC, 40A at 230VAC
Cold start, 30A at 115VAC, 60A at 230VAC
Fixed
General Specification (Please refer to www.meanwell.com for detail spec.)
MDR-100
AC input voltage range
10% rated output voltage
0~+20% rated output voltage
AC inrush current
>105% hiccup mode, auto-recovery
105%-160% constant current
limiting, auto-recovery
105%~150% constant current limiting, auto-recovery
Over voltage protection
15%~135% rated output voltage
125%~150% rated output voltage
Setup, rise, hold up time
500ms, 30ms, 120ms
3000ms, 50ms, 50m
500ms, 30ms, 50ms
Withstand voltage
I/P-O/P:3kVAC, I/P-FG:2kVAC, 1minute
Working temperature
-20~+70°C (refer to output derating curve)
-10~+60°C
DC OK signal
Open collector
Relay contact
Safety standards
UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1 approved; MDR-40/60 also approved for UL62368-1, ANSI/ISA 12.12.01-2013 Class I, Div. 2 Group A, B, C, D Hazardous Locations T4
EMC standards
BS EN/EN55032 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 heavy industry level (MDR-40/60/100), CNS13438
Connection
I/P: 3 poles, O/P: 3 poles screw DIN terminal
Dimension (WxHxD)(mm)
22.5x90x100
IP: 3 poles, O/P: 6 poles screw DIN terminal
40x90x100
55x90x100
20W
15V, 0~1.34A
Model No
Output
Tol.
R&N
Effi.
MDR-10-5
5V, 0~3.0A
±2%
80mV
76.%
MDR-10-15
12V, 0~1.67A
120mV
80.%
MDR-20-12
24V, 0~1.00A
±1%
120mV
81.%
MDR-20-24
±1%
±1%
150mV
84.%
40W
Model No
Output
Tol.
R&N
Effi.
MDR-40-5
5V, 0~6.00A
±2%
80mV
78%
12V, 0~3.33A
120mV
86%
MDR-40-12
±1%
MDR-40-48
MDR-40-24
24V, 0~1.70A
48V, 0~0.83A
±1%
±1%
150mV
200mV
88%
88%
Effi.
R&N
Tol.
Output
Model No
100 W
Model No
Output
Tol.
R&N
Effi.
MDR-100-12
12V, 0~7.5A
±1%
120mV
83%
MDR-100-24
24V, 0~4.0A
±1%
150mV
86%
MDR-100-48
48V, 0~2.0A
±1%
200mV
87%