Security Series
40~60W Single Output with Battery Charger
Features
-
Single output with built-in battery charger circuit (UPS function)
-
Universal AC input / Full range
-
Can be installed on DIN rail TS-35/7.5 or 15
-
Protections:
Short circuit / Overload / Over voltage / Battery low protection /
Battery reverse polarity protection by fuse
-
Alarm signal for AC OK and battery low via RELAY Contact
-
Pass LPS
-
LED indicator for power on
-
3 years warranty
DRC-40
DRC-60
40W
DRC-40
Model No
Output
Tol.
Effi.
R&N
DRC-40A
13.8V, 0~2.9A
±1%
40W
DRC-40B
13.8V, 0~1.0A
27.6V, 0~1.45A
Model No
DRC-40
DRC-60
AC input voltage range
90~264VAC; 127~370VDC
AC inrush current (max.)
Cold start, 30A at 115VAC, 60A at 230VAC
General Specification (Please refer to www.meanwell.com for detail spec.)
DC adjustment range
105%~135% rated output voltage
400ms, 50ms, 50ms at full load and 230VAC
Withstand voltage
Working temperature
-30~+70°C (refer to output derating curve)
Safety standards
UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS62368.1 approved
EMC standards
BS EN/EN55032 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EAC TP TC 020
I/P:3 poles, O/P: 8 poles
Connection (screw DIN terminal)
I/P: 3 poles, O/P: 3 poles screw DIN terminal
Dimension (LxWxH)(mm)
CH1,13.8V: 12~15V; 27.6V:24~30V
Overload protection
Over voltage protection
Setup, rise, hold up time
I/P-O/P:3kVAC, I/P-FG: 2kVAC, O/P-FG: 0.5kVAC
27.6V, 0~0.5A
Max.
±1%
(Charger)
(Charger)
120mV
200mV
86%
87%
40W
60W
DRC-60
Model No
Output
Tol.
Effi.
R&N
DRC-60A
13.8V, 0~4.3A
±1%
59W
DRC-60B
13.8V, 0~1.5A
27.6V, 0~2.15A
27.6V, 0~0.75A
Max.
±1%
(Charger)
(Charger)
120mV
200mV
86%
88%
59W
DRS Series Example of Application
Security Series
100~180W Single Output with Battery Charger
Features
-
Single output with built-in battery charger crrcuit
(UPS function)
-
Universal AC input / Full range
-
Can be installed on DIN rail
TS-35/7.5 or 15
-
Protections:
Short circuit / Overload / Over voltage / Battery low
protection / Battery reverse polarity protection by fuse
-
Alarm signal for AC OK and battery low via
RELAY contact
-
Fanless design
-
LED indicator for power on
-
3 years warranty
NDR-120
NDR-120
Model No
DRC-100
DRC-180
AC input voltage range
90~264VAC; 127~370VDC
AC inrush current (max.)
Cold start, 30A at 115VAC, 60A at 230VAC
General Specification (Please refer to www.meanwell.com for detail spec.)
DC adjustment range
105%~135% rated output voltage
2400ms, 50ms, 50ms at full load and 230VAC
Withstand voltage
Working temperature
-30~+70°C (refer to output derating curve)
Safety standards
UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS62368.1 approved
CH1,13.8V: 12~15V; 27.6V:24~30V
105%~150% hiccup mode, auto-recovery
Overload protection
Over voltage protection
Setup, rise, hold up time
I/P-O/P:3kVAC, I/P-FG: 2kVAC, O/P-FG: 0.5kVAC
100W
DRC-100
Model No
Output
Tol.
Effi.
R&N
DRC-40A
13.8V, 0~7A
±1%
97W
DRC-40B
13.8V, 0~2.5A
27.6V, 0~3.5A
27.6V, 0~1.25A
Max.
±1%
(Charger)
(Charger)
120mV
240mV
87%
89%
97W
Cold start, 35A at 115VAC, 70A at 230VAC
CH1:13.8V:12~15V; 27.6V:24~29V
2000ms, 20ms, 20ms at full load and 230VAC
-20~+70°C (refer to output derating curve)
Safety standards
BS EN/EN55032 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EAC TP TC 020
Connection (screw DIN terminal)
I/P:3 poles, O/P: 10 poles
180W
DRC-180
Model No
Output
Tol.
Effi.
R&N
DRC-180A
13.8V, 0~9A
±1%
180W
DRC-180B
27.6V, 0~4.5A
27.6V, 0~2A
Max.
±1%
(Charger)
(Charger)
150mV
240mV
88%
90%
180W
13.8V, 0~4A
I/P:3 poles, O/P:8 poles
Dimension (LxWxH)(mm)
55x 90x 100
63x 125.2x 113.5
AC OK
DRS Series Example of Application
RELAY Closed
when the power supply turns ON
when the power supply turns OFF
RELAY Open
RELAY Open
when the voltageof battery is under A:11V,B:22V
when the voltageof battery is above A:11V,B:22V
RELAY Closed
Battery Low